BASIC CABLE SIZING FOR MOTORS |
|
||
| Table is for 480 V, 3 phase motors in magnetic conduit, 90 C cable, no direct sunlight, maximum 2% voltage drop running, maximum 10% voltage drop on starting. | |||
HP |
FLA |
Cable Size |
Cable O.D. (in) |
NEC Conduit Size (in) |
Max. Distance (ft) |
Starter Size (Local) |
Feeder Breaker (TM) Size for Local Starter |
||
| 0.5 | 1.1 | 1/3/10 | 1 - .049 | 0.75 | 2491 | 1 or 00 | 15 | ||
| 0.75 | 1.6 | 1/3/10 | 1 - .049 | 0.75 | 1713 | 1 or 00 | 15 | ||
| 1 | 2.1 | 1/3/10 | 1 - .049 | 0.75 | 1305 | 1 or 00 | 15 | ||
| 1.5 | 3 | 1/3/10 | 1 - .049 | 0.75 | 989 | 1 or 00 | 15 | ||
| 2 | 3.4 | 1/3/10 | 1 - .049 | 0.75 | 1048 | 1 or 00 | 15 | ||
| 3 | 4.8 | 1/3/10 | 1 - .049 | 0.75 | 825 | 1 or 0 | 15 | ||
| 5 | 7.6 | 1/3/10 | 1 - .049 | 0.75 | 586 | 1 or 0 | 15 | ||
| 7.5 | 11 | 1/3/10 | 1 - .049 | 0.75 | 486 | 1 | 20 | ||
| 10 | 14 | 1/3/10 | 1 - .049 | 0.75 | 382 | 1 | 30 | ||
| 15 | 21 | 1/3/10 | 1 - .049 | 0.75 | 254 | 2 | 40 | ||
| 20 | 27 | 1/3/08 | 1 0.67 | 1 | 307 | 2 | 50 | ||
| 25 | 34 | 1/3/06 | 1 0.77 | 1 | 387 | 2 | 60 | ||
| 30 | 40 | 1/3/06 | 1 0.77 | 1 | 329 | 3 | 80 | ||
| 40 | 52 | 1/3/04 | 1 0.89 | 1.5 | 402 | 3 | 100 | ||
| 50 | 65 | 1/3/02 | 1 1.02 | 1.5 | 503 | 3 | 125 | ||
| 60 | 77 | 1-3-1/0 | 1 1.22 | 2 | 654 | 4 | 150 | ||
| | | 3-1-1/0 | 3 0.629 | 2 | | | | ||
| 75 | 96 | 1-3-1/0 | 1 1.22 | 2 | 525 | 4 | 175 | ||
| | | 3-1-1/0 | 3 0.629 | 2 | | | | ||
| 100 | 124 | 3-1-4/0 | 3 0.785 | 2.5 | 666 | 4 | 250 | ||
| 125 | 156 | 3-1-4/0 | 3 0.785 | 2.5 | 529 | 5 | 300 | ||
| 150 | 180 | 3-1-350 | 3 0.985 | 3 | 430 | 5 | 350 | ||
| 200 | 240 | 3-1-500 | 3 1.032 | 3.5 | 345 | 5 | 400 | ||
| 250 | 302 | 6-1-4/0 | 6 0.785 | 3 | 555 | 6 | 500 | ||
| 300 | 361 | 6-1-350 | 6 0.985 | 4 | 427 | 6 | 600 | ||
| 350 | 414 | 6-1-350 | 6 0.985 | 4 | 372 | 6 | 700 | ||
| 400 | 477 | 6-1-500 | 6 1.032 | 5 | 344 | 6 | 800 | ||
| 450 | 515 | 6-1-500 | 6 1.032 | 5 | 318 | 7 | 900 | ||
| 500 | 590 | 9-1-350 | 9 0.985 | 5 | 392 | 7 | 1000 |